Bul. 937C Universal Temperature Converter Installation Instructions
The following parameters can be set:
Sensor (see Connection section):
Resistance temperature detector: Pt10GOST etc.
Thermocouple: TXK etc.
Potentiometer
Voltage
Connection mode (for resistance temperature detectors only, see Connection section):
2-wire
3-wire
4-wire
Unit:
for resistance temperature detectors and thermocouples: °F, K or °C
for potentiometers: fixed ratio
for voltage (sources): fixed mV
The unit selected here will be used for all respective settings and displays in PACTware
TM
.
Cold junction compensation (for thermocouples only):
external (Reference temperature)
internal (Bul 937A-TCJC)
If you have selected Ext. ref. temp., you can enter the external reference temperature
(range of values: -100 °C to 320 °C)
For an internal Cold junction compensation, you require the Bul 937A-TCJC terminal block as
an accessory instead of the normal terminal 1 to 3 (see Connection section).
Lead Resistance: When connecting an RTD with 2 wire connection the lead resistance of the
cabling can be entered numerically if known.
2-Wire Calibration: When connecting an RTD with 2-wire connection the lead resistance of the
cabling can be calibrated if the resistance is unknown. For calibration the sensor must be jumpered.
Sensor-breakage monitoring (for all types of sensors)
Sensor-short-circuit monitoring (for resistance temperature detectors only)
You activate or deactivate monitoring by clicking the respective checkbox
( = selected, = deselected).