User Manual User guide
Programming Instruction References
A-19
Instruction Description Parameter Valid Addressing
Mode(s)
Valid File Types Immediate
Values
SUS Suspend suspend ID -32,768-32,767
SVC
➆
Service
Communications
channel 0 (SLC
5/03 and SLC 5/04)
0=no, 1=yes
channel 1 (SLC
5/03 and SLC 5/04)
0=no, 1=yes
SWP
➁
Swap source indexed direct
indexed indirect
B, N, A, ST none
length 1-128: bit,
1-128: integer,
1-41: string,
1-128: ASCII
TAN
➁
Tangent source direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
-32,768-32,767
fmin-fmax
destination direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, F, A, ST, M
none
TND Temporary End none
TOD Convert to BCD source direct, indexed direct
indirect, indexed indirect
O, I, S, B, T, C, R,
N, A, ST, M
none
destination direct O, I. S. B. T, C, R,
N, A, ST, M
none
TOF Timer Off Delay timer direct T none
time base (SLC
5/01)
0.01 only
time base (SLC
5/02, SLC 5/03,
SLC 5/04,
MicroLogix 1000
controllers)
0.01 or 1.00
preset 0-32,767
accum 0-32,767
➁
Supported
only by SLC 5/03 OS302 and SLC 5/04 OS401 processors.
➆
Supported only by SLC 5/02, SLC 5/03, and SLC 5/04 processors.