USER MANUAL APS 6.0

Preface
Advanced Programming Software User Manual
13–14
Parameter Description
Diagnostic File Reserved for future use.
Baud Rate
Toggles between the communication rate of 110, 300, 600, 1200,
2400, 4800, 9600, and 19200.
Parity Toggles between None and Even. The default is None.
Stop Bits Toggles between 1, 1.5, and 2. The default is 1.
Station Address The valid range is 0-254 decimal. The default is 1.
Duplicate Packet Detection Toggles between Enabled and Disabled. The default is Enabled.
Error Detection Toggles between CRC and BCC. The default is CRC.
ACK Timeout
Allows you to select the ACK timeout value in increments of 20 ms.
The valid range is 0-65535.
RTS Off Delay
Allows you to select the RTS off delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
Message Retries
Allows you to select the message retries value. The valid range is
0-255. The default is 3.
RTS Send Delay
Allows you to select the RTS send delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
Presend Time Delay
Allows you to select the RTS pretransmit time delay in increments
of 20 ms. The valid range is 0-65535.
Control Line
Toggles between No Handshaking, FullDuplex Modem, and
HalfDuplex Without Continuous Carrier.
Polling Mode
Toggles between Message Based (Do Not Allow Slave to Initiate
Messages), Message Based (Allow Slave to Initiate Messages),
Standard (Single Message Transfer Per Node Scan), and Standard
(Multiple Message Transfer Per Node Scan).
Priority Polling - Low
Allows you to select the Priority Polling Range Low Address. The
valid range is 0-255.
Normal Polling - Low
Allows you to select the Normal Polling Range Low Address. The
valid range is 0-255.
Priority Polling - High
Allows you to select the Priority Polling Range High Address. The
valid range is 0-254.
Normal Polling - High
Allows you to select the Normal Polling Range High Address. The
valid range is 0-254.
Reply Message Wait Time
Allows you to select the Reply Message Wait Time setting in
increments of 20 ms. The valid range is 0-65535.
Normal Poll Group Size
Allows you to select the Normal Poll Group Size. The valid range
is 0-255.