USER MANUAL APS 6.0

Preface
Advanced Programming Software User Manual
13–12
DF1 Half-Duplex Slave Channel 0 Configuration
When the system mode driver is DF1 Half-Duplex Slave for channel 0 the following
screen is displayed:
Communication Driver: DF1 HALF-DUPLEX SLAVE
Diagnostic File: Reserved
Baud Rate: 1200 Parity: NONE
Stop Bits: 1
Station Address: 0
Duplicate Detect: ENABLED Error Detect: CRC
RTS Off Delay [x20 ms]: 0
RTS Send Delay [x20 ms]: 0
Poll Timeout [x20 ms]: 50 Pre-send Time Delay [x1 ms]: 65535
Message Retries: 0
Control Line: NO HANDSHAKING EOT Suppression: NO
F2
UNDO
EDITS
Press a key for desired status function
REM PROG no forces EDITS: NONE PROC Addr 1
Channel 0 System Mode Configuration
F1
ACCEPT
EDITS
F9
CHANNEL
STATUS
F10
SELECT
OPTION
You can configure the DF1 Half-Duplex Slave driver even if the Current
Communication Mode of channel 0 is set to User
.
Parameter Description
Diagnostic File Reserved for future use.
Baud Rate
Toggles between the communication rate of 110, 300, 600, 1200,
2400, 4800, 9600, and 19200. The default is 1200.
Parity Toggles between None and Even. The default is None.
Stop Bits Toggles between 1, 1.5, and 2. The default is 1.
Station Address The valid range is 0-254 decimal. The default is 1.
Duplicate Packet Detection Toggles between Enabled and Disabled. The default is Enabled.
Error Detection Toggles between CRC and BCC. The default is CRC.
RTS Off Delay
Allows you to select the RTS off delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
RTS Send Delay
Allows you to select the RTS send delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
Poll Timeout
Allows you to select the master poll timeout value in increments of
20 ms. The default is 50. The valid range is 0-65535.
Presend Time Delay
Allows you to select the RTS pretransmit time delay in increments
of 20 ms. The valid range is 0-65535.