USER MANUAL APS 6.0
Preface
Advanced Programming Software User Manual
13–2
Configuring SLC 5/01 and SLC 5/02 Processors
APS versions 2.0 and later support DH-485 point-to-point communication. Y
ou can
connect APS to the SLC 500 processors using a 1747-PIC Interface Converter
, a
1770-KF3 module, or 1747-KE module. A 1747-AIC Link Coupler is required for
DH-485 network communication.
APS
SLC 500
Modular I/O Controller
1747–PIC
Interface Converter
The parameters that must be configured for online communication are explained
below.
Note The
SLC 5/01 and SLC 5/02 pr
ocessors stor
e their node addr
esses and baud rates in
word S:15. W
e r
ecommend making these parameters part of your user pr
ogram.
This pr
events unauthorized (or unintended) alteration of your pr
ogram. Refer to the
system status file in the
Instruction Set Reference Manual
for mor
e information
about wor
d S:15.
Node Address
Each device on the DH-485 network must have a unique node address. The default
node address for APS is 0, and the default for the processors is 1. T
o change a
processor node address, write a value between 1 and 31 using the Who function.
The change is applied immediately.
Baud Rate
Each DH-485 network device must have a common baud rate. The table below
shows the available baud rates. Y
ou must cycle power to apply the new baud rate.
Processor Baud Rate
Fixed and SLC 5/01 9600 or 19200
SLC 5/02 1200, 2400, 9600, or 19200