USER MANUAL APS 6.0
Preface
Advanced Programming Software User Manual
11–36
Example Configuration: PI Routing
SLC 5/04 processor
Station 3
(octal)
APS 6.0 or later
Node 77
(octal)
Station 15
(octal)
CH1
Node 1
(octal)
DH+
Link ID=1
57,600 baud
DH+
Link ID=2
57,600 baud
Pyramid Integrator
t
Current Device 1784-KT (DH+ Bridged)
F1 Bridge Type PI Routing
Terminal Name
Terminal Address 77 (octal)
Baud Rate 57600
F5 Remote Node Addr. 1 (octal)
F6 PI DH+ Address 3 (octal)
F7 PI Remote Link ID 2 (decimal)
IRQ 5
Board/Memory Address 001011
F8 Curr. Interchange Port 1
F9 Save to File
F9
Press a function key
SAVE TO
FILE
ESC exits/Alt-U aborts changes
ONLINE CONFIGURATION
F8
NEXT
PORT
F5
REMOTE
ADDRESS
F2
SELECT
DEVICE
F1
SELECT
BRIDGE
F6
PI DH+
ADDRESS
F7
REMOTE
LINK ID
Function Key Description
[F1] Select Bridge Type
Allows you to select the desired bridge type: DH+ to DH+ via
two 1785KA, DH+ to DH485 via 1785 KA5 Gateway, PI
routing, or DH+ to Channel 0 via 5/04 passthru.
[F2] Select Device
Toggles between the selected device driver and the device
driver selection menu.
[F5] Remote Node Address
Allows you to enter the processor address. Valid range is
0–77 octal. The default is 1.
[F6] PI DH+ Address
Allows you to enter the PI DH+ address. Valid range is 0–77
octal. The default is 7.
[F7] Remote Link ID
Allows you to enter the Remote link ID. Valid range is
1–65,535 decimal. The default is 2.
[F8] Next Port
Allows you to select the port number where the interface card
is installed. Valid range is 1–8. The default is 1.
[F9] Save to File Saves the selected parameters to a user file.