USER MANUAL APS 6.0
Preface
Advanced Programming Software User Manual
11–10
1784-KL (DH+ Bridged) Interface Card
The 1784-KL (DH+ Bridged) interface card requires one of the following devices to
establish communication with an SLC processor:
• 1785-KA5 DH+/DH-485 gateway module to bridge the DH+ and DH-485 data
links (required for all SLC 500 processors)
• 1747-PIC Interface Converter when using an SLC 5/04 processor configured for
DH-485 communication via channel 0 (RS-232)
Current Device 1784-KL (DH+ Bridged)
F3 Connection DIRECT
F4 Terminal DH+ Address 0 (octal)
F5 SLC Node Address 1 (decimal)
F6 KA5 DH+ Address 1 (octal)
F9 Save to File
F9
Press a function key
SAVE T0
FILE
F5 F6
SLC
ADDRESS
KA5
ADDRESS
F3
CONNECT
TYPE
F2
SELECT
DEVICE
F4
TERM
ADDRESS
ESC exits/Alt-U aborts changes
ONLINE CONFIGURATION
Function Key Description
[F2] Select Device
Toggles between the selected interface card and the interface
card selection menu.
[F3] Connect Type
Toggles between Direct and MultiDrop. Direct means that the
terminal has a termination resistor (last device on the DH+
link). MultiDrop means that the terminal does not have a
termination resistor. The default is Direct.
[F4] Terminal Address
Allows you to select a terminal address on DH+ as a node
number from 0–77 octal. The default is 0.
[F5] SLC Address
This is the default address of the processor the APS terminal
attempts to go online with. Valid range is 0–31 decimal. The
default is 1.
[F6] KA5 Address
Allows you to select a KA5 address on DH+ as a node number
from 0-77 octal. The default is 1.
[F9] Save to File
Allows you to save the established parameters to a user
configuration file that APS accesses to automatically set up
these parameters the next time you use the software.