Analog Output status with alarm
Usermayselectoutputvalueunderfaultcondi
tions
OutputcompliantwithNAMURrecommenda
tions(NE43)canbeset(<3.6mAor>21mA)
Input fault detection
Inputfaultssuchasshortcircuitoropencircuitcan
bedetectedformostinputtypes.Theseareshown
inthe
tablebelow.
Input type Detection
Open cir-
cuit
Short cir-
cuit
Thermocouple Yes Yes
RTD Yes Yes
Millivolts Yes No
Volts(Positive) Yes No
Milliamps
(Passive)
Yes* No
Milliamps(Ac
tive)
Yes Yes
Resistance Yes Yes
Potentiometer Yes Yes**
Table2 Inputfaultdetection
* Opencircuitnotdetectedforlivezeroranges
**Shortcircuitforendtoend