Manual
10
4. Mounting
The signal conditioners are mounted on standard TS 35 rails.
5. Electrical connection
5.1 Technical Data
Supply voltage 18 ... 30 Vdc/approx. 1 W
Operating temperature 0 °C ... +55 °C
Voltage supply via cross-connections. Operating carrying capacity of cross-
connection 2 A
Klemmenbelegung
1 Eingang + > 5 mA
2 Eingang + ≤ 500 mV / ≤ 5 mA
3 Eingang + > 500 mV
4 Eingang -
5 Ausgang +
6 Ausgang -
7 Versorgungsspannung
8 Versorgungsspannung
A
nschlußquerschnitt max. 2,5 mm
2
Mehrleiteranschluß max. 1 mm
2
(zwei Leiter gleichen Querschnitts)
78
10
1
2
3
9
11
12
Terminal assignments
1 Thermo +
2 not assigned
3 Thermo –
7 Output + 0/4…20 mA
8 Output + 0…10 V
9 Output 0 V
10 Power supply + 24 Vdc (cross connected)
11 Power supply GND (cross connected)
12 not assigned
Wire cross-section max. 2.5 mm
2
Multi-wire conncection max. 1 mm
2
(two wires with same cross-section)