Manual

1010
4. Mounting
The signal conditioners are mounted on standard TS 35 rails.
5. Electrical connection
5.1 Technical Data
Supply voltage 18 ... 30 Vdc/approx. 1 W
Operating temperature 0 °C ... +55 °C
Voltage supply via plug-in jumper. Operating carrying capacity of
cross-connection ^ 2 A
Terminal assignments
1 +15 V power supply for sensor
2 Input PNP
3 Input NPN / Namur
4 Input GND
5 Output (0...10 V; 0/4...20 mA)
6 Output GND
7 Supply voltage + 24 Vdc (cross-connected)
8 Power supply GND (cross-connected)
Wire cross-section max. 2.5 mm
2
Multi-wire conncection max. 1 mm
2
(two wires with same cross-section)
6
7
1
2
8
3
4
5