6. Technical Data
Input 0 ... 20 mA
Input voltage max. 15 V
Operating current < 100 μA
Voltage drop 2.5 ... 3 V (at 20 mA)
Input overload capacity max. 50 mA, 15 V
Output 0 ... 20 mA, max. 10 V
Load 500 Ω
Response time approx. 5 ms for a load of 500 Ω
(to reach 99% program value)
Residual ripple < 10 mV
eff
General data
Chopper frequency approx. 200 kHz
Transmission errors < 0.1 % of end value + 0.05 % of
measured value / 100 Ω load
Temperature effect
1)
50 ppm/K from measured value
for a load of 0 Ω
Test voltage
Input / output 510 V AC, 50 Hz
EMC
2)
EMC directive
EN 61 326
EN 61 326/A1
Ambient temperature
Operation -25 °C ... +60 °C
Storage -40 °C ... +85 °C
1) Medium temperature coefficient in the specified
operating temperature range (-25 °C ... +60 °C)
2) Valid for 4 ... 20 mA; minor deviations are possible
during interferences.