GETTING STARTED Owner manual

Setting Up ControlNet to RIO Block Transfer Pass Thru Communications 8-7
Using RS-232 to
ControlNet to RIO
Block Transfer
Pass Thru
Communications
RS-232 to ControlNet to RIO Block Transfer Pass Thru communications use an
external converter (1770-KFC).
Important:
If you are using an interface card, refer to “Using ControlNet to
RIO Block Transfer Pass Thru Communications” on page 8-3.
Hardware
Required Hardware
The hardware required for this type of communications depends on the drive
type. Refer to the following table:
Setting Up the Hardware
To use DriveTools32 with this type of communications, you must:
Ensure that the drive and adapter are properly installed and powered.
Ensure that cables are securely connected and protected from damage.
Ensure that block transfer is enabled in your adapter. If you are using a
1203-Gx1 or 1336-GM1 module, switch 1 on SW3 must be ON.
Important:
Ensure that the ladder logic program and PLC configuration reflect
the image table with Block Transfer enabled.
Note the Remote I/O adapter settings. You need to specify the rack and
group number when configuring a DriveTools32 application.
Drive Required Drive Hardware Required Computer Hardware
SCANport Product
Remote I/O adapter (1203-GD1,
1203-GK1, or 1336-GM1) and
appropriate cable(s)
1770-KFC and RS-232 port
1336 FORCE PLC Communications Adapter Board
(1336T-GT1EN)
1770-KFC and RS-232 port
1395 Node Adapter (1395-KP50) or
Multi-Communications Adapter
(1395-KP51)
1770-KFC and RS-232 port
For a list of SCANport-compatible products, refer to Appendix A,
Products Supported by DriveTools32
.
If Using: Refer To:
Remote I/O Adapter (1203-GD1, 1203-GK1 or
1336-GM1) and appropriate cable(s)
Bulletin 1203 Remote I/O Communications Module User
Manual
PLC Communications Adapter Board
(1336T-GT1EN)
1336 FORCE PLC Communications Adapter User Manual
Node Adapter (1395-KP50) or
Multi-Communications Adapter (1395-KP51)
Bulletin 1395 Multi-Communications Board Hardware/
Software Reference Manual