GETTING STARTED Owner manual

Setting Up DH+ to RIO Block Transfer Pass Thru Communications 6-7
Using RS-232 to
DH+ to RIO Block
Transfer Pass Thru
Communications
RS-232 to DH+ to RIO Pass Thru communications require an external converter
(1770-KF2).
Important:
If you are using an internal interface card, refer to “Using DH+ to
RIO Block Transfer Pass Thru Communications” on page 6-3.
Hardware
Required Hardware
The hardware required for this type of communications depends on the drive
type. Refer to the following table:
Setting Up the Hardware
To use DriveTools32 with this type of communications, you must:
Ensure that the drive and adapter are properly installed and powered.
Ensure that cables are securely connected and protected from damage.
Ensure that block transfer is enabled in your adapter. If you are using a
1203-Gx1 or 1336-GM1 module, switch 1 on SW3 must be ON.
Important:
Ensure that the ladder logic program and controller configuration
reflect the image table with Block Transfer enabled.
Note the Remote I/O adapter settings. You need to specify the rack and
group number when configuring a DriveTools32 application.
Drive Required Drive Hardware Required Computer Hardware
SCANport-Compatible
Remote I/O Adapter (1203-GD1,
1203-GK1 or 1336-GM1) and
appropriate cable(s)
RS-232 port and 1770-KF2
1336 FORCE PLC Communications Adapter Board
(1336T-GT1EN)
RS-232 port and 1770-KF2
1395 Node Adapter (1395-KP50) or
Multi-Communications Adapter
(1395-KP51)
RS-232 port and 1770-KF2
For a list of SCANport-compatible products, refer to Appendix A,
Products Supported by DriveTools32
.
Adapter Refer To:
Remote I/O Adapter (1203-GD1, 1203-GK1 or
1336-GM1) and appropriate cable(s)
Bulletin 1203 Remote I/O Communications Module User
Manual
PLC Communications Adapter Board
(1336T-GT1EN)
1336 FORCE PLC Communications Adapter User Manual
Node Adapter (1395-KP50) or
Multi-Communications Adapter (1395-KP51)
Bulletin 1395 Multi-Communications Board Hardware/
Software Reference Manual