GETTING STARTED Owner manual

10-8 Setting Up Allen-Bradley Ethernet to RIO Block Transfer Pass Thru Communications
3.
In the
Enter Starting Group #
field, type the RIO starting group number of
the drive. The RIO starting group number is set in the communications
module. Valid numbers are 0, 2, 4, and 6.
4.
If you are using a 1395 drive, click
Use 1395 Protocol
.
5.
In the
Enter SN/B Slot Number
field, type the scanner slot number. Type 0
if you are using a PLC. Type the appropriate slot number if you are using an
SLC.
6.
Click
OK
.
The DriveTools32 application is now communicating with the drive. If you are
prompted to create a new database, click
Ye s
.
Important:
If a prompt appears to alert you that the application failed to
communicate with the drive, refer to Chapter 16,
Troubleshooting
.