GETTING STARTED Owner manual
Setting Up Allen-Bradley Ethernet to RIO Block Transfer Pass Thru Communications 10-7
4.
Under
Connect Type
, select
Allen-Bradley Ethernet to PLC (SLC) with
RIO pass-thru
.
Important:
If you are running DriveMonitor32, you can access a PLC by
selecting
Allen-Bradley Ethernet Direct to PLC
.
5.
In the
Enter IP Address
field, type the same IP address entered in the
Configure driver for Ethernet to PLC-5 or 5820
dialog box.
6.
If you are using a 1336 FORCE and its drive firmware version is 0.10,
select
1336T Two Word Header (used ONLY for 1336T version 0.10)
.
7.
Click
OK
. The following prompt appears.
8.
Read the information, and then click
OK
.
Connecting to the
Drive
After configuring RSLinx and the DriveTools32 application, you are ready to
connect to a drive.
1.
In the
Drive
menu, select
Connect to Drive
. The
Ethernet Connect to
Drive
dialog box appears.
2.
In the
Enter Drive Rack #
field, type the RIO rack number of the drive.
The rack number is specified in octal and is set in the communications
module.