User guide

Publication 900-UM007D-EN-E - January 2011
Configuration & Basic Operation 3-19
Figure 3.22
2. The Input Type is displayed. When you are monitoring/configuring the
Input Type for the first time, the set value is 0: K type thermocouple
default. (0 is set if you have a platinum resistance thermometer
compatible controller. To select a different sensor, press the U or D
keys. This changes the Set Value (refer to Table 3.A) to match your
desired sensor input.
Figure 3.23
3. Select the Temperature Unit parameter by pressing the M key. Note:
The default is c: °C. To configure f: °F, press the U key.
Figure 3.24
4. Select the Control Period (OUT1) parameter by pressing the M key.
Note: The default is 20.
Figure 3.25
5. Select the Direct/Reverse Operation parameter by pressing the M key.
Note: The default is or-r: reverse operation. To configure or-d:
direct operation, press the U key.
Figure 3.26
C
30
0
in-t
5
Input type
d-u
c
Temperature unit
cp
20
Control period
(heat)
orev
or-r
Direct/reverse
operation