Preparations 2-23
(LBA) and Heater Short Alarm (HSA) that are provided for the Bulletin
900 Controller.)
Figure 2.20
Select a surge absorber that satisfies the following conditions.
Control Output 2
• For 900-TC8 & 900-TC16: Output 2 is applied from terminals 11 and
12 or 14 and 15 with the 900-TC16, and from pins 14 and 15 with the
900-TC8. The following diagrams show the available outputs and their
equal internal circuits.
Figure 2.21
➊ Option Unit: 900-TC16P1V2
➋ Option Unit: 900-TC16NCOMV2
The following table shows the specifications for each output type.
Table 2.G
Voltage Used Varistor Voltage Surge Resistance
100…120V AC 240…270V 1,000 A min.
200…240V AC 440…470V
Table 2.H — 900-TC8
Output Type Output 2 Specifications
Triac (AC) relay 250V AC, 3 A (resistive load), electrical durability: 1,000,000
operations
Voltage (PNP) PNP type, 12V DC +15%/−20%, 21 mA (with short-circuit
protection)