C-18 Calibration
Checking Indication
Accuracy
After calibrating input, make sure to check indication accuracy to make
sure that the Bulletin 900 Controller has been correctly calibrated.
Operate the Bulletin 900 Controller in the PV/SP monitor mode.
Check the indication accuracy at the Upper- and Lower-Limits and
mid-point.
Checking Accuracy of a Thermocouple or Non-Contact
Temperature Sensor
Preparation: The following figure shows the required device
connection. Make sure that the Bulletin 900 Controller and cold
junction compensator are connected by a compensating conductor for
the thermocouple that is to be used during actual operation. For the
non-contact temperature sensor, connect a K thermocouple, and
configured the Input Type to the K thermocouple.
Figure C.36
Cold Junction Compensator
Input Power Supply
Compensation Conductor
900-TC8
1
2
19
20
-
+
STV
Cold Junction Compensator
Input Power Supply
Compensation Conductor
900-TC16
9
10
4
5
-
+
STV
Cold Junction Compensator
Input Power Supply
Compensation Conductor
900-TC32
1
2
11
12
-
+
STV