User guide
Publication 900-UM007D-EN-E - January 2011
B-13
PV/Display Screen
Selection
spdp
0: PV/SP
1: PV/SP/Multi-SP, PV/SP/MV
2: PV/SP/MV, PV/SP/Multi-SP
3: PV/SP/Multi-SP
4: PV/SP/MV
5: PV/SP/Multi-SP, PV/SP/
Soak Time Remain
6: PV/SP/MV, PV/SP/Soak
Time Remain
7: PV/SP/Soak Time Remain
4 None
MV Display Selection odsl
O: MV (Heating)
C-O: MV (Cooling)
o
c-o
0 None
PV Decimal Point
Display
pvdp OFF, ON off on ON None
PV Status Display
Function
pvst
OFF: OFF
MANU: Manual
STOP: Stop
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
ALM: Alarm 1 to 3 OR status
HA: Heater alarm
off
manu
stop
alm1
alm2
alm3
alm
ha
OFF None
SV Status Display
Function
svst
OFF: OFF
MANU: Manual
STOP: Stop
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
ALM: Alarm 1 to 3 OR status
HA: Heater alarm
off
manu
stop
alm1
alm2
alm3
alm
ha
OFF None
Display Refresh Period d.ref OFF, 0.25, 0.5, 1.0 .25 Second
Control Output 1
ON/OFF Count Monitor
ra1m 0....9999 0 100 times
Control Output 2
ON/OFF Count Monitor
ra2m 0....9999 0 100 times
Control Output 1 ON/
OFF Count Alarm Set
Value
ra1 0....9999 0 100 times
Table B.F — Advanced Setting Function Group
Parameters Characters Setting (Monitor) Value Display Default Unit Set Value