User guide

Publication 900-UM007D-EN-E - January 2011
B-12
Table B.F — Advanced Setting Function Group
Parameters Characters Setting (Monitor) Value Display Default Unit Set Value
PV Rate of Change
Calculation Period
pvrp 1...999 4 Sampling
period
Automatic Cooling
Coefficient Adjustment
csca OFF, ON off on OFF None
Heater Overcurrent Use 0cu OFF, ON off on ON None
Heater Overcurrent
Latch
ocl OFF, ON off on OFF None
Heater Overcurrent
Hysteresis
och 0.1...50.0 0.1 A
PF Setting pf OFF: OFF
RUN: RUN
STOP: STOP
R-S: RUN/STOP
AT-2: 100% AT execute/cancel
AT-1: 40% AT execute/cancel
LAT: Alarm Latch Cancel
A-ML Auto/manual
PFDP: Monitor/Setting Item
off
run
stop
r-s
at-2
at-1
lat
a-m
pfdp
A-M None
Monitor/Setting Item 1 pfd1
0: Disabled
1: PV/SP/Multi-SP
2: PV/SP/MV
3: PV/SP/Soak time remain
4: Proportional band (P)
5: Integral time (I)
6: Derivative time (D)
7: Alarm value 1
8: Alarm value upper limit 1
9: Alarm value lower limit 1
10: Alarm value 2
11: Alarm value upper limit 2
12: Alarm value lower limit 2
13: Alarm value 3
14: Alarm value upper limit 3
15: Alarm value lower limit 3
1 None
Monitor/Setting Item 2 pfd2 0...15, same as Monitor Setting
Item 1
0 None
Monitor/Setting Item 3 pfd3 0...15, same as Monitor Setting
Item 1
0 None
Monitor/Setting Item 4 pfd4 0...15, same as Monitor Setting
Item 1
0 None
Monitor/Setting Item 5 pfd5 0...15, same as Monitor Setting
Item 1
0 None