User guide
Publication 900-UM007D-EN-E - January 2011
B-11
—
Table B.F — Advanced Setting Function Group
Parameters Characters Setting (Monitor) Value Display Default Unit Set Value
LBA Detection Time lba 0…9999
(0: LBA function disabled)
0 Second
LBA Level lbal Universal input: 0.1…999.9 8.0 °C or °F ➊
Analog input: 0.01…99.99 10.00 %FS
LBA Band lbab Universal input: 0.0…999.9 3.0 °C or °F ➊
Analog input: 0.00…99.99 0.20 %FS
Control Output 1
Assignment
out1 When Control Output 1 is a
voltage (SSR) output: ➋
NONE: No assignment
O: Control output (heating)
C-O: Control output (cooling)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
P.END: Program end output ➌
RALM: Control output ON/OFF
count alarm ➍
none
o
c-o
alm1
alm2
alm3
p.end
ralm
O None
When Control Output 1 is a linear
analog output: ➋
NONE: No assignment
O: Control output (heating)
C-O: Control output (cooling)
none
o
c-o
Control Output 2
Assignment
out2 NONE: No assignment
O: Control output (heating)
C-O: Control output (cooling)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
P.END: Program end output ➊
RALM: Control output ON/OFF
count alarm ➍
none
o
c-o
alm1
alm2
alm3
p.end
ralm
NONE None
Auxiliary Output 1
Assignment
sub1 Same as Control Output 1 (except
fixed as a relay output)
ALM1 None
Auxiliary Output 2
Assignment
sub2 Same as Control Output 1 ALM2 None
Auxiliary Output 3
Assignment (900-TC8)
sub3 Same as Control Output 1 ALM3 None
Character Select csel OFF, ON off on ON None
Soak Time Unit t-u M: Minutes; H: Hours m h M None
Alarm SP Selection alsp
SP-M: Ramp set point
SP:
Set point
sp-m
sp
SP-M None
Manual MV Limit manl OFF, ON off on ON None