User guide
Publication 900-UM007D-EN-E - January 2011
B-5
Table B.C — Initial Setting Function Group
Parameters Characters Setting (Monitor) Value Display Default Unit Set Value
SP Lower-Limit sl-l Input range Lower-Limit to SP
Upper-Limit − 1 (temperature)
−200 EU
Scaling Lower-Limit to SP Upper-Limit
− 1 (analog)
0
PID ON/OFF intl ON/OFF 2-PID onof
pid
ON/OFF None
Standard or
Heating/Cooling
s-hc Standard or heating/cooling send
h-c
Standard None
ST st OFF, ON off on ON None
Program Pattern ptrn OFF, STOP, CONT off
stop
cont
OFF None
Control Period
(Heating)
cp 0.5 or 1…99 0.5
1 to 99
20 Second
Control Period (Cooling) c-cp 0.5 or 1…99 0.5
1 to 99
20 Second
Direct/Reverse
Operation
orev Reverse operation, direct operation or-r
or-d
Reverse
operation
None