Set NONE as the unit for controllers with 0…50 Millivolt Inputs.
Table B.B — Adjustment Function Group
Parameters Characters Setting (Monitor) Value Display Default Unit Set
Value
Dead Band c-db Universal input: 199.9…999.9 0.0 °C or °F
Analog input: 19.99…99.99 0.00 %FS
Manual Reset Value of-r 0.0…100.0 50.0 %
Hysteresis (heating) hys Universal input: 0.1…999.9 1.0 ° C or °F
Analog input: 0.01…99.99 0.10 %FS
Hysteresis (cooling) chys Universal input: 0.1…999.9 1.0 ° C or °F
Analog input: 0.01…99.99 0.10 %FS
Soak Time soak 1…9,999 1 min or h
Wait Band wt-b Universal input: OFF, 0.1…999.9 off
0.1 to
999.9
OFF °C or °F
Analog input: OFF, 0.01…99.99 off
0.01 to
99.99
OFF %FS
MV at Stop mv-s 5.0…105.0 (standard)
105.0…105.0 (heating/cooling)
0.0 %
MV at PV Error mv-e 5.0…105.0 (standard)
105.0…105.0 (heating/cooling)
0.0 %
SP Ramp Set Value sprt OFF or 1…9,999 off
1 to 9999
OFF EU/s,
EU/min
MV Upper-Limit ol-h MV Lower-Limit +0.1 /105.0 (standard)
0.0…105.0 (heating/cooling)
105.0 %
MV Lower-Limit ol-l 5.0 to MV Upper-Limit 0.1 (standard)
105.0…0.0 (heating/cooling)
5.0 (standard)
105.0 (heating/
c
ooling)
%
MV Change Rate
Limit
orl 0.0...100.0 (0.0: MV Change Rate Limit
Disabled)
0.0 %/s
Extraction of Square
Root Low-cut Point
sqrp 0.0...100.0 0.0 %