Table B.B — Adjustment Function Group
Parameters Characters Setting (Monitor) Value Display Default Unit Set Value
Adjustment Level Display l.adj
AT Execute/Cancel at OFF, AT Cancel AT-2: 100%
AT Execute AT-1: 40% AT
Execute
off
at-2
at-1
OFF None
Communications Writing cmwt OFF, ON off on OFF None
Heater Current 1 Value Monitor ct1 0.0…55.0 A
Heater Overcurrent Detection 1 oc1 0.0…50.0 50.0 A
Heater Current 2 Value Monitor ct2 0.0…55.0 A
Heater Overcurrent Detection 2 oc2 0.0…50.0 50.0 A
Leakage Current 1 Monitor lcr1 0.0…55.0 A
HS Alarm 1 hs1 0.0…50.0 50.0 A
Leakage Current 2 Monitor lcr2 0.0…55.0 A
HS Alarm 2 hs2 0.0…50.0 50.0 A
Heater Burnout Detection 1 hb1 0.0…50.0 0.0 A
Heater Burnout Detection 2 hb2 0.0…50.0 0.0 A
SP 0 sp-0 SP Lower-Limit to SP
Upper-Limit
0EU
SP 1 sp-1 SP Lower-Limit to SP
Upper-Limit
0EU
SP 2 sp-2 SP Lower-Limit to SP
Upper-Limit
0EU
SP 3 sp-3 SP Lower-Limit to SP
Upper-Limit
0EU
Temperature Input Shift ins −199.9…999.9 0.0 °C or °F
Upper-Limit Temperature Input
Shift Value
insh −199.9…999.9 0.0 °C or °F
Lower-Limit Temperature Input
Shift Value
insl −199.9…999.9 0.0 °C or °F
Proportional Band p Universal input:
0.1…999.9
8.0 °C or °F ➊
Ana
log input: 0.1…999.9 10.0 %FS
Integral Time i 0…3,999 233 Second
Derivative Time d RT OFF: 0…3,999 40 Second
RT ON: 0.0…999.9 40.0 Second
Cooling Coefficient c-sc 0.01…99.99 1.00 None