The default is 5 (°C/°F) for Controllers with Thermocouple/Resistance
Thermometer Universal Inputs and 0 for Controllers with Analog
Inputs.
The applicable standards for each of the above input ranges are as
follows:
K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PLII: According to Platinel II Electromotive Force Table by
Engelhard Corp.
Control Range
Resistance thermometer and thermocouple input Temperature lower
limit -20 °C to temperature upper limit +20 °C, or temperature lower
limit -40 °C to temperature upper limit +40 °C
Infrared input: same as input indication range
Analog input: -5% to +105% of scaling range