User guide
Publication 900-UM007D-EN-E - January 2011
A-3
The indication of K thermocouples in the −200…1,300°C range, T and N thermocouples at a temperature of
−100°C or less, and U and L thermocouples at any temperature is ±2°C ±1 digit maximum. The indication of B
thermocouples at a temperature of 400°C or less is not specified.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
Ambient temperature: −10°C…23°C…55°C
Voltage range: −15…+10% of rated voltage
Table A.A (Continued)
Technical/Control (Continued)
Indication Accuracy
(ambient temperature of 23°C)
Thermocouple :
(±0.3% of indication value or ±1 °C, whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2% of indication value or ± 0.8 °C, whichever is greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Temperature Variation
Influence
Thermocouple (R, S, B, W, PL II)
(±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouples:
(±1% of PV or ±4°C, whichever is greater) ±1 digit max.
*K thermocouple at −100°C max: ±10°C max.
Platinum resistance thermometer:
(±1% of PV or ±2 °C, whichever is greater) ±1 digit max.
Analog input: ±1% FS ±1 digit max.
Voltage Variation Influence ✟
General/Environmental
Insulation Rresistance 20 MΩ min. (by 500V DC megger)
Dielectric Strength 2300V AC 50 or 60 Hz 1 min. (between terminals of different function)
Vibration Operating
10…55 Hz, 20 m/s
2
(2 G) for 10 min. each in X, Y, and Z directions
Non-
operating
10…55 Hz,20 m/s
2
for 2 hrs. each in X, Y, and Z directions
Shock Operating
100 m/s
2
(10 G) max., 3 times in each X, Y, Z axes directions.
Non-
operating
300 m/s
2
(30 G) max., 3 times in each 3 axes, 6 directions.
Protective Structure Front
panel
IP66
Rear case IP20, terminals: IP00 (VDE 0106)
Memory Protection EEPROM (non-volatile memory) (number of writes: 100,000)
Approximate Weight
in grams
(includes carton)
Total Unit Adapter Terminal Cover
900-TC8 260 100
1.6 per cover
900-TC16 150 10
10
900-TC32 90 10
—
Ambient Temperature –10…+55 °C (with no condensation or icing)