User guide

Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions 5-109
Function: This parameter resets the ON/OFF counter for specified control
outputs.
Note: After the counter has been reset, the count value will be automatically
returned to 0.
Related Parameter
Control output 1 ON/OFF count monitor, Control output 2 ON/OFF
monitor (Advanced Setting function group, page 5-107)
Move to Calibration Group
Conditions of Use: Initial Setting/Communications Protect parameter must
be set to 0.
Function: This parameter allows you to configure the Password to Move to
the Calibration function group.
Set the Password to Move to the Calibration function group. The
password is 1201.
Move to the Calibration function group either by pressing the
M key or
the
O key or by waiting for 2 seconds to elapse.
Related Parameter
Initial Setting/Communications Protect (Protect function group, page
5-4)
Communications Setting
Function Group
This function group allows you to configure the controller’s communication
parameters, enabling interface to a personal computer that is running the
controller configuration or monitoring software. The controller hardware must
support communications through a RS232 option module (900-TC8) or
RS485 option module (900-TC8, 900-TC16, and 900-TC32).
Table 5.EJ
Selections Default
0: Disable the counter reset function
01: Reset the control output 1 ON/OFF counter
2: Reset the control output 2 ON/OFF counter
cmov