PV/SP Display Screen Selection
Conditions of Use: The No. 3 display must be supported (900-TC8)
Function: This parameter allows you to configure what will be displayed on
the PV/SP Screen No. display and the order of the display. The default is 4.
Note: A 2- level display is set at the time of shipping from the factory (set
value = 0). A 3- level display is activated if parameters are initialized (set
value =4).
Related Parameter
Process Value Set Point (Operation function group, page 5-8)
MV Display Selection (Advanced Setting function group, page 5-103)
MV Display Selection
Conditions of Use: The No. 3 display must be supported(900-TC-8). Heating
and cooling control must be used. The PV/SP Display Screen Selection
parameter must be set to 1, 2, 4, or 6, or the Monitor/Setting Item 1 to 5
parameter must be set to 2.
Table 5.DZ
Set Value Display Contents
0 Only PV/SP is displayed (with no No. 3 display).
1 PV/SP/Multi-SP and PV/SP/MV are displayed in order
2 PV/SP/MV and PV/SP/Multi-SP are displayed in order
3 Only PV/SP/Multi-SP is displayed.
4 PV/SP/MV is displayed
5 PV/SP/Multi-SP and PV/SP/Soak time remain are displayed in order
6 PV/SP/MV and PV/SP/Soak time remain are displayed in order
7 Only PV/SP/Soak time remain is displayed.
The MV for heating and cooling control is configured in the MV Display Selection parameter.