5-102 Parameter Functions & Definitions
Monitor/ Setting Item
* (*: 1 to 5)
Conditions of Use: The PF Setting parameter must be configured to PFDP.
Function: When you configure the PF Key parameter to Monitor/Setting
Item it enables using the function key to display monitor/setting items. The
items that will be displayed are configured using the Monitor/Setting Item 1 to
5 parameters. The settings are listed in the following table.
Note: The MV for heating and cooling control is set in the MV Display
Selection parameter.
Related Parameter
PF Setting (page 5-101), MV Display Selection (page 5-103) (Advanced
Setting function group)
Table 5.DY
Set Value Parameter
Remarks
Monitor/Setting Symbol
0 Disabled ---
1 PV/SP/Multi-SP Can be set. (SP) ---
2 PV/SP/MV Can be set. (SP) ---
3 PV/SP/Soak time remain Can be set. (SP) ---
4 Proportional band (P) Can be set. p
5 Integral time (I) Can be set. c
6 Derivative time (D) Can be set. d
7 Alarm value 1 Can be set. al-1
8 Alarm value upper limit 1 Can be set. al 1h
9 Alarm value lower limit 1 Can be set. al il
10 Alarm value 2 Can be set. al-2
11 Alarm value upper limit 2 Can be set. al2h
12 Alarm value upper limit 2 Can be set. al2l
13 Alarm value lower limit 2 Can be set. al-3
14 Alarm value 3 Can be set. al3h
15 Alarm value upper limit 3 Can be set. al3l
pfd*