Parameter Functions & Definitions 5-101
Related Parameters
• Heater overcurrent use (Advanced Setting function group, page 5-99)
PF Setting
Conditions of Use: The PF Key must be supported (900-TC8)
Function: This parameter allows you to configure which function the PF Key
will have.
Related Parameters
• Monitor/setting item 1 to 5 (Advanced Setting function group, page
5-102)
Table 5.DX
Set Value Setting Function
OFF: off Disabled Does not operate as a function key
RUN: run RUN Specifies RUN status.
STOP: stop STOP Specifies STOP status.
R-S: r-s Reversing
RUN/STOP
operation
Specifies Reversing RUN/STOP operation status.
AT-2: at-2 100% AT
Execute/Cancel
Specifies reversing 100% AT Execute/Cancel
status ➊
AT-1: at-1 40% AT
Execute/Cancel
Specifies reversing 40% AT Execute/Cancel
status ➊
LAT: lat Alarm Latch
Cancel
Specifies canceling alarm latches ➋
A-M: a-m Auto/Manual Specifies reversing Auto/Manual status ➌
PFDP: pfdp Monitor/Setting
Item
Specifies the monitor/setting item display. Select
the monitor/setting item using the
Monitor/Setting Item 1 to 5 parameters
(Advanced Setting function group).
➊ When AT cancel is specified, it means that AT is cancelled regardless of whether the AT currently being
executed is 100% AT or 40% AT.
➋ Alarms 1 to 3, heater burnout, HS alarms, and heater overcurrent latches are cancelled.
➌ For details on auto/manual operations using the PF Key, refer to Performing Manual Control
pf