5-100 Parameter Functions & Definitions
Function: When you configure this parameter to ON, the HS alarm is held
until any of the following conditions is satisfied:
Heater overcurrent detection is set to 50.0 A.
The controller power is cycled.
The latch is cancelled by the PF Key. (900-TC8) PF Setting = LAT:
Alarm Latch Cancel
The latch is cancelled by an event input. (Event Input Assignment 1 and
2 = LAT: Alarm Latch Cancel)
Note: The output is turned OFF when switching to the Initial Setting function
group, Communications function group, Advanced Setting function
group, or calibration function group.
Related Parameters
Heater overcurrent detection 1, Heater overcurrent detection 2
(Adjustment function group, page 5-26)
Heater overcurrent use (Advanced Setting function group, page 5-99)
Heater overcurrent hysteresis (Advanced Setting function group, page
5-100)
Event input assignment 1 and 2 (Initial Setting function group, page
5-66)
HB ON/OFF: page 5-74, PF setting (Advanced Setting function group,
page 5-101)
Heater Overcurrent Hysteresis
(900-TC8, 900-TC16)
Conditions of Use: Heater burnout, HS alarms, and heater overcurrent
detection must be supported, and alarm 1 must be assigned. The Heater
Overcurrent Use parameter must be set to ON, and the Heater Overcurrent
Latch parameter must be set to OFF.
Function: This parameter allows you to configure the hysteresis (allowed
deviation from setting) for heater overcurrent detection.
Table 5.DV
Selections Default
on: Enabled, off: Disabled off
Table 5.DW
Configurable Range Units Default
0.1 to 50.0 A 0.1