User guide
Publication 900-UM007D-EN-E - January 2011
5-96 Parameter Functions & Definitions
Related Parameters
• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
(Initial Setting function group)
Character Select LED
Function: This parameter allows you to select the LED display type for your
controller. The following two types of displays are available:
• 11-segment display
• 7-segment display
When set to
on, an 11-segment display is used.
Soak Time Units
Conditions of Use: The Program Pattern parameter must NOT be set to
OFF.
Table 5.DO
Auxiliary Output 3 Function Default
none: No function is assigned to auxiliary output 3 alm3 ➌
o: Heating Control Output is output
c-o: Cooling Control Output is output➊
alm1: Alarm 1is output
alm2: Alarm 2 is output
alm3: Alarm 3 is output
p.end: Program end is output➋
ralm: Control output ON/OFF count alarm➋
➊ If c-o is assigned for standard control, a value equivalent to 0% will be output.
➋ Can be selected only when the program pattern is not set to OFF, but the function is disabled.
➌ If the Standard or Heating/Cooling parameter is set to heating/cooling control when there is no Control Output
2 (900-TC8), control automatically switches to
c-o.
Table 5.DP
Selections Default
on: 11-segment display, off: 7-segment display on
csel
t-u