Parameter Functions & Definitions 5-95
Note: If the Standard or Heating/Cooling parameter is set to heating/cooling
control, this parameter will automatically be set to c-o (900-TC32).
Related Parameters
• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
(Initial Setting function group)
Auxillary Output 3 Assignment
Conditions of Use: Auxiliary Output 3 must be assigned (900-TC8 only).
Function: This parameter allows you to configure the function assigned to
Auxiliary Output 3.
Table 5.DN
Auxiliary Output 2 Function Default
none: No function is assigned to auxiliary output 2 alm2➌
(see note to
follow)
o: Heating Control Output is output
c-o: Cooling Control Output is output➊
alm1: Alarm 1is output
alm2: Alarm 2 is output
alm3: Alarm 3 is output
p.end: Program end is output➋
ralm: Control output ON/OFF count alarm➋
➊ If c-o is assigned for standard control, a value equivalent to 0% will be output.
➋ Can be selected only when the program pattern is not set to OFF.
➌ If the Standard or Heating/Cooling parameter is set to heating/cooling control when there is no Control
Output 2 (900-TC16), control automatically switches to
c-o.
sub3