5-92 Parameter Functions & Definitions
Related Parameters
Process Value/Set Point (Operation function group, page 5-8)
Alarm 1 Type (Initial Setting function group, page 5-59)
LBA Detection Time, LBA Level (Advanced Setting function group,
page 5-90)
Control Output 1 Assignment
Conditions of Use: The Transfer Output Type parameter must be set to OFF
when the Control Output is an analog current output.
Function: This parameter allows you to configure the output function
assigned to Control Output 1.
Related Parameters
Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
Transfer Output Type (page 5-62) (Initial Setting function group)
Table 5.DK
Control Output 1 Function Default
None: No control output function is assigned o
o: Heating control output is output
c-o: Cooling control output is output
alm1: Alarm 1 is output
alm2: Alarm 2 is output
alm3: Alarm 3 is output
p.end: Program end is output➋➌
ralm: Control output ON/OFF count alarm
If c-o (cooling Control Output) is assigned for standard control, a value equivalent to 0% is output.
Can be selected for relay and voltage outputs only
Can be selected only when the program pattern is not set to OFF, but the function is disabled.
out1