5-90 Parameter Functions & Definitions
Function: This parameter allows you to configure the hysteresis (allowed
deviation from setting) for the operation of the Heater Short Alarm (HSA).
Related Parameter
HS Alarm Use (Advanced Setting function group, page 5-88)
Loop Break Alarm (LBA) Detection Time
Conditions of Use: Alarm 1 must be assigned. The Alarm Type must be set
to 12 (LBA).
Function: This parameter allows you to enable or disable the LBA function
and set the detection time interval. To disable the LBA function, set it to 0.
Note: For more details concerning the LBA Detection Time refer to
Section 4, Loop Break Alarm on page 4-47.
Related Parameters
Alarm 1 Type (Initial Setting function group, page 5-59)
LBA Level (page 5-90), LBA Band (page 5-91) (Advanced Setting
function group)
Loop Break Alarm (LBA) Level
Conditions of Use: Alarm 1 must be assigned. The Alarm Type must be set
to 12 (LBA). The LBA detection time must NOT be 0.
Table 5.DG
Configurable Range Units Default
0.1…50.0 A (Amps) 0.1
Table 5.DH
Configuration Range Units Default
0…9999 Seconds 0
lba