5-80 Parameter Functions & Definitions
Function: When this parameter is set to ON, the alarm function is held until
one of the following conditions are satisfied:
The power to the controller is cycled.
The latch is cancelled by the PF Key. (PF Setting = LAT: Alarm Latch
Cancel)
The latch is cancelled by an event input.(Event Input Assignment 1 and
2 = LAT: Alarm Latch Cancel)
The output is turned OFF when switching to the Initial Setting function
group, communications function group, Advanced Setting function
group, or calibration level.
If an auxiliary output is set to close in alarm, the output is kept closed. If
it is set to open in alarm, it is kept open.
Related Parameters
Alarm Value 1 to 3 (Operation function group, page 5-16)
Upper-Limit Alarm Value 1 to 3, Lower-Limit Alarm Value 1 to 3
(Operation function group, page 5-20)
Alarm 1 to 3 Type (Initial Setting function group, page 5-59)
Standby Sequence Reset Method (Advanced Setting function group,
page 5-72)
Auxiliary Output 1 to 3 Open in Alarm, (Advanced Setting function
group, page 5-73)
Event input assignment 1 and 2 (Initial Setting function group, page
5-66) HB ON/OFF: (page 5-74), PF setting: (page 5-101) (Advanced
Setting function group)
Protect Function Group Move Time
Function: This parameter allows you to configure the control panel key
pressing time required to move to the Protect function group from the
Operation function group, Adjustment function group, or Monitor/Setting
function group.
Table 5.CS
Selections Default Selection
on: ON
off: OFF
off
prlt