HB ON/OFF (900-TC8, 900-TC16)
Conditions of Use: The controller hardware that supports the Heater
Burnout (HB), Heater Short (HS), and Heater Overcurrent (HO), Alarm 1
must be configured and the appropriate number of Current Transformers
(CT) to support the application are connected to the controller.
Function: This parameter allows you to configure the operation of the Heater
Burnout Alarm (HBA).
Heater Burnout Latch (900-TC8, 900-TC16)
Conditions of Use: The HB ON/OFF parameter must be configured to ON
and the controller hardware must support the Heater Burnout (HB), Heater
Short (HS), and heater overcurrent detection. Alarm 1 must also be configured
to ON. The appropriate number of Current Transformers (CT) to support the
application must be connected to the controller.
Function: When this parameter is configured to ON, the heater burnout
alarm is held ON until one of the following reset conditions are satisfied:
The Alarm Output is turned OFF when switching to the Initial Setting
function group, Communications Setting function group, Advanced
Setting function group, or Calibration function group, or
Heater burnout detection is set to 0.0 A, or
Controller power is cycled from ON to OFF.
The latch is canceled by the PF key (900-TC8 only). PF Setting = LAT:
Alarm Latch Cancel.
The latch is canceled by an event input. (Event Input Assignment 1 and
2 = LAT: Alarm Latch Cancel).
Table 5.CI
Selections Default Selection
on: Alarm Enabled
off: Alarm Disabled
on
hbu
hbl