The following table shows the functions assigned when an Event Input
Assignment (1 or 2) is displayed.
Note: 1 PRST (Program Start) can be configured even when the Program Pat-
tern parameter is configured to OFF, but the function will be dis-
abled.
Note: 2 This function can be configured for heating/cooling control, but the
function will be disabled.
When any of the following functions are configured for an Event Input
Assignment parameter, the same function cannot be configured for
another Event Input Assignment parameter: STOP (RUN/STOP),
MANU (Auto/Manual Switch), PRST (Program Start), DRS (Invert
Direct/Reverse Operation), AT-2 (100% AT Execute/Cancel), AT-1
(40% AT Execute/Cancel), WTPT (Setting Change Enable/Disable), or
LAT (Alarm Latch Cancel).
Related Parameters
SP0 to SP3 (Adjustment function group, page 5-33),
Event input assignment 1 and 2 (Initial Setting function group, page
5-66), Multi-SP use (Advanced Setting function group, page 5-71)
Event Input Assignment (
* 1 and 2)
(900-TC8,
900-TC16)
Conditions of Use: An event input unit must be installed in the controller.
Multi-SP must NOT be used.
Table 5.CB
Selection Function
none None
stop RUN/STOP
manu Auto/Manual Switch
prst Program start (see note 1.)
drs Invert Direct/Reverse Operation
at-2 100% AT Execute/Cancel
at-1 40% AT Execute/ Cancel (see note 2)
wtpt Setting Change Enable/Disable
lat Alarm Latch Cancel
ev-*