Parameter Functions & Definitions 5-63
Note: Calibration is NOT supported for the transfer output.
Related Parameter
Transfer Output Upper-Limit, Transfer Output Lower-Limit (Initial
Setting function group, page 5-63)
Transfer Output Upper-Limit
Transfer Output Lower-Limit
Conditions of Use: An analog current output must be assigned/configured.
The Transfer Output Type parameter must NOT be set to OFF.
Function: This parameter allows you to configure the Upper- and
Lower-Limit values specifically for the transfer output and separate from the
actual function (e.g., Set Point Limits).
Table 5.BT — Transfer Output Destination
Control Output 1 Type Control Output 2 Type
Transfer Output
Destination
Current Output No
Relay Output
Voltage Output (for driving SSR)
Control Output 1
Relay Output
Voltage output (for
driving SSR)
•No
Relay Output
Voltage Output (for driving SSR)
No
Table 5.BU
Transfer Output Type Selection Default
OFF off off
Set point sp
Set point during SP ramp sp-m
PV pv
MV monitor (heating) mv
MV monitor (cooling) c-mv
tr-h
tr-l