5-48 Parameter Functions & Definitions
(900-TC8) the PV, SP and the Manual MV can be displayed if the third
parameter is enabled (refer to the following graphics displays)
Related Parameters
Standard or Heating/Cooling (Initial Setting function group, page 5-55)
Initial Setting Function
Group
This function group is for configuring the basic parameters of the Bulletin 900
controller. In this function group, you can configure the Input Type parameter
for selecting the sensor input to be connected to the Bulletin 900 controller,
limit the range of set points, or set the alarm mode, and perform other
operations.
Table 5.BB
Monitor Range Units
Process value Temperature: According to indication range for
each sensor.
Analog: Scaling lower limit -5% FS to Scaling
upper limit +5% FS
EU
Set Point SP lower limit to SP upper limit EU
Table 5.BC
Configurable Range Units
MV (manual MV) Standard control 5.0…105.0 %
Heating/cooling control 105.0…105.0
When the MV Limit Enable Parameter is configured to ON, the configurable range will be the MV Lower Limit
to MV Upper Limit.
PV/SP/Manual MV
25
100
50.0
MANU
With No. 3 Display
C
25
50.0
MANU
C
Without No. 3 Display
25
MANU
50.0
C
Note: When the PV/SP Display screen selection parameter is 0.
in-t