5-40 Parameter Functions & Definitions
Wait Band
Conditions of Use: The Program Pattern parameter must NOT be set to
OFF.
Function: This parameter enables you to configure the stable band within
which the soak time is measured for the simple program function.
Set NONE as the unit for Controllers with 0…50 Millivolt Inputs.
Related Parameters
Program Start, Soak Time Remain (Operation function group, page
5-15)
Soak Time (Adjustment function group, page 5-39)
Program Pattern (Initial Setting function group, page 5-57)
Soak Time Unit (Advanced Setting function group, page 5-96)
MV at Stop
Conditions of Use: The control method must be configured for 2-PID
control. The MV at Stop and Error Addition parameter must be configured to
ON.
Function: This parameter allows you to configure the amount the MV
(process output) is OPEN/ON when the RUN/STOP status changes from
RUN to STOP.
Table 5.AS
Controller Type
Configurable
Range Units Default
With Thermocouple or Resistance
Thermometer (RTD)
OFF or
0.1…999.9
°C or °F
Off
With Analog Inputs OFF or
0.01…99.99
%FS
Table 5.AT
Configurable Range Units Default
5.0…105.0 for standard control
105.0…105.0 (heating/cooling control)
%0.0
wt-b