User guide
Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions 5-33
Related Parameters
Refer to the Advanced Setting function group:
• Leakage Current 2 Monitor (page 5-14)
• HS Alarm Use, HS Alarm Latch, HS Alarm Hysteresis (page 5-88)
Set Point 0
Set Point 1
Set Point 2
Set Point 3
Conditions of Use: The Number of Multi-SP Uses parameter must be
configured to either 1 or 2, and the Multi-SP Uses parameter must be
configured to ON.
Function: These parameters allow you to configure multiple (up to 4) set
point values as long as the Multi-SP function is also configured.
For 900-TC8 or 900-TC16, the configured values configured in these 4
parameters can be selected (loaded into the controller) by operating the keys
on the front panel or by event input.
Table 5.AJ
• While operating (RUN) if a change is made to a set point (SP 0, SP 1,
SP 2, or SP 3) it takes effect approximately 2 seconds after entering the
value, or upon depressing the or
M key.
• When using a temperature input, the decimal point position is
dependent on the selected sensor.
• When using an analog input, the decimal point position is dependent on
the setting of the Decimal Point position parameter.
Configurable Range Units Default Value
Set Point Lower-Limit to Set Point Upper-Limit EU 0
sp-0
sp-1
sp-2
sp-3