Parameter Functions & Definitions 5-29
ffff is displayed when 55.0 A is exceeded.
If a HS alarm 1 alarm is output, the HA indicator will light, and the
leakage current value will flash on the No. 1 display.
Related Parameters
Refer to the Advanced Setting function group:
HS Alarm 1, HS Alarm 2 (page 5-31)
HS Alarm Use (page 5-88)
Error Displays
lcr1
Leakage Current 2 Monitor (900-TC8, 900-TC16)
Conditions of Use: Heater Burnout (HBA) and Heater Short (HSA) alarms
and heater overcurrent detection must be supported (two CTs). Alarm 1 must
be assigned. The HS Alarm parameter must be set to ON.
Function: This parameter measures the heater current from two CT inputs
used for detecting a short-circuit condition.
This parameter measures and displays the heater current value.
Note: A Heater Short fault condition is not detected if its duration is 100 ms
or less.
ffff is displayed when 55.0 A is exceeded.
If an HS alarm 2 alarm is output, the HA indicator will light and the No.
1display for the leakage current 2 monitor will flash.
Table 5.AD
Monitoring Range Units
0.0…55.0 A (Amps)
Table 5.AE
Monitoring Range Units
0.0…55.0 A (Amps)
lcr2