5-14 Parameter Functions & Definitions
Table 5.O
HS alarm is not detected if the Control Output (heating) OFF time is
100 ms or less.
ffff is displayed when 55.0 A is exceeded.
If an HS alarm 1 alarm is output, the HA indicator will light and the No.
1display for the leakage current 1 monitor will flash.
Related Parameters
Refer to the Advanced Setting function group:
HS Alarm 1, HS Alarm 2 (page 5-31)
Failure Detection (page 5-88)
Error Displays
lcr1 (Chapter 6, page 6-5)
Leakage Current 2 Monitor
(900-TC8 &900-TC16)
Conditions of Use: Heater Burnout (HBA), Heater Short (HSA), and Heater
Overcurrent (HOA) alarms must be supported and two CTs (Number 1 and
Number 2) wired to the controller. Alarm 1 must be assigned. The HS Alarm
Use parameter must be set to ON.
Function: This parameter measures and displays the heater current from two
CT inputs used for detecting short-circuit conditions in 3-phase heaters.
This parameter measures and displays the heater current value.
HS alarm is not detected if the Control Output (heating) OFF time is
100 ms or less.
ffff is displayed when 55.0 A is exceeded.
If an HS alarm 2 alarm is output, the HA indicator will light and the No.
1display for the leakage current 2 monitor will flash.
Monitoring Range Units
0.0…55.0 A (Amps)
Table 5.P
Monitoring Range Units
0.0…55.0 A (Amps)
lcr2