User guide

Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions 5-13
Function: This parameter measures the heater current from two CT inputs
used for detecting heater alarm conditions in 3-phase heaters and displays the
value on the controller.
Heater burnout, heater short, and heater overcurrent conditions are not
detected if the Control Output (heating) ON time is 100 ms or less.
ffff is displayed when 55.0 A is exceeded.
If a heater burnout detection 2 or heater overcurrent detection 2 alarm
is output, the HA indicator will light and the No. 1 display for the heater
current 2 value monitor will flash.
Related Parameters
Refer to the Advanced Setting function group:
Heater Burnout Detection 1, Heater Burnout Detection 2 (page 5-30)
HB ON/OFF (page 5-30)
Heater overcurrent detection 1, Heater overcurrent detection 2 (page
5-30)
Heater overcurrent use (page 5-30)
Error Displays
ct2: (Chapter 6, page 6-5)
Leakage Current 1 Monitor
(900-TC8 &900-TC16)
Conditions of Use: Heater Burnout (HBA), Heater Short (HSA), and Heater
Overcurrent (HOA) alarms must be supported. Alarm 1 must be assigned and
CT Number 1 wired to the controller. The HS Alarm Use parameter must be
set to ON.
Function: This parameter measures the heater current from the Number 1
CT input used for detecting a short-circuit condition in single-phase heaters.
The heater current is measured and the value is displayed.
Table 5.N
Monitoring Range Units
0.0...55.0 A (Amps)
lcr1