4-76 Parameter Adjustments & Application Considerations
Note: The order of priority is as follows: Manual MV > MV at stop > MV at
PV error.
MV at PV Error
You can configure the amount the MV is output during an input error
condition. The MV at stop takes priority when stopped and the manual MV
takes priority in manual mode.
Note: The order of priority is as follows: Manual MV > MV at stop > MV at
PV error.
The order of priority of the MVs is illustrated in the following diagram.
Figure 4.166
Table 4.AH
Parameter Configurable Range Unit Default
MV at Stop 5.0…105.0 for standard control
105.0…105.0 (heating/cooling control)
%0.00
Table 4.AI
Parameter Configurable Range Unit Default
MV at PV error 5.0…105.0 for standard control
105.0…105.0 (heating/cooling control)
%0.0
PID
calculations
MV upper limit
Manipulated variable
Time
MV lower limit
MV at PV Error
Input error
RUN/STOP
MV at Stop
Manual MV
Auto/manual switch
Output
1