User guide

Publication 900-UM007D-EN-E - January 2011
Parameter Adjustments & Application Considerations 4-71
1. Press the O key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.153
2. Select the Program Pattern parameter by pressing the M key.
Figure 4.154
3. Use the U key to set the parameter to STOP.
Figure 4.155
4. Press the O key for at least 1 second to move from the Initial Setting
function group to the Operation function group.
Figure 4.156
5. Press the O key to move from the Operation function group to the
Adjustment function group.
Figure 4.157
6. Select the Soak Time parameter by pressing the M key.
Figure 4.158
in-t
5
Input type
ptrn
off
Program Pattern
ptrn
stop