4-66 Parameter Adjustments & Application Considerations
Using the Simple Program
Function
Simple Program Function
The simple program function can be used to perform a simple one step ramp
and soak operation.
Figure 4.146
The simple program will start when the Program Start parameter is changed
from RSET to STRT. END will be displayed on the No. 2 display and the
output assigned as the program end output will turn ON after the time
configured in the Soak Time parameter has expired in the wait band. The
Program Pattern parameter can be used to select moving to STOP mode or
continuing operation in RUN mode after the program ends.
The configurable units for the Wait Band parameter is %FS for Controllers with Analog Inputs and the range is
OFF or 0.01…99.99.
Units configured for Controllers with Thermocouple/Resistance Thermometer Multi-inputs. Set NONE as the
unit for Controllers with Analog Inputs.
RSET STRT
PV
SP
Set point
Wait band
Wait band
Soak time END display
END output
Select either
STOP or RUN.
Table 4.AF —Parameters Related to the Simple Program Function
Parameter Name Symbol Configurable (Monitor) Values Units
Display Function
Group
Program Pattern ptrn OFF, STOP, CONT Initial Setting
Program Start prst RSET, STRT Operation
Soak Time soak 1…9999 min or h Adjustment
Soak Time Unit t-u m (minutes)/h (hours) Advanced Setting
Wait Band wt-b OFF or 0.1…999.9 °C or °F ➊ ➋ Adjustment
Soak Time Remain Monitor sktr 0…9999 min or h Operation