User guide

Publication 900-UM007C-EN-E - January 2011
Preface P-v
Body Removal
900-TC8, 900-TC16, &
900-TC32 Ratings
Table P.D — Body Removal
Series A Series B
900-TC8
Removal using screws
Removal using hooks
900-TC16 --- No change for body removal
900-TC32 --- No change for body removal
Table P.E — 900-TC8, 900-TC16, & 900-TC32 Ratings
Series A Series B
Input sensor types for thermocouple inputs
---
The following types of thermocouple input
were added: W and PLII.
Input range for E thermocouple: 0...600 ºC
Input range increased for E thermocouple:
-200...600 ºC
Input accuracy
Thermocouple: ±0.5% PV or ±1ºC,
whichever is greater) ±1 digit
Platinum resistance thermometer:
(±0.5%PV or ±1ºC, whichever is
greater) ± 1 digit
Analog input: ±0.5% FS ± digit
Thermocouple: ±0.3% PV or ±1ºC,
whichever is greater) ±1 digit
Platinum resistance thermometer:
(±0.2%PV or ±.08ºC, whichever is
greater) ± 1 digit
Analog input: ±0.2% FS ± digit