User guide

Publication 900-UM007D-EN-E - January 2011
4-52 Parameter Adjustments & Application Considerations
5. Press the D key to enter the password (169), and move from the
Initial Setting function group to the Advanced Setting function group.
Figure 4.101
6. Select the LBA Detection Time parameter by pressing the M key.
Figure 4.102
7. Press the U key to set the parameter to 10.
Figure 4.103
8. Select the LBA Level parameter by pressing the M key.
Figure 4.104
9. Press the U key to set the parameter to 8.0. (Note: The default is 8.0.)
10. Select the LBA Band parameter by pressing the M key.
Figure 4.105
11. Press the U or D key to set the parameter to 3.0. (Note: The default is
3.0.)
Figure 4.106
init
off
Parameter
initialization
lba
0
LBA detection
time
C
lba
10
C
lbal
8.0
LBA level
C
lbal
8.0
C
lbab
3.0
LBA band
C
lbab
3.0